Issue 01/06 Parameter Description
MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0
111
Index:
P1000[0] : 1st. Command data set (CDS)
P1000[1] : 2nd. Command data set (CDS)
P1000[2] : 3rd. Command data set (CDS)
Example:
Setting 12 selects main setpoint (2) derived from analog input with additional setpoint (1) taken from the
motor potentiometer.
P1000 =
1
2
⇒
P1070 = 755
P1070 CI: Main setpoint
r0755 CO: Act. ADC after scal. [4000h]
P1000 = 1
2
⇒
P1075 = 1050
P1075 CI: Additional setpoint
r1050 CO: Act. Output freq. of the MOP
Example P1000 = 12 :
MOP
ADC
FF
USS
BOP link
USS
COM link
CB
COM link
ADC2
P1000 =
1
2
P1000 = 1
2
Sequence control
Main
setpoint
Setpoint
channel
Motor
control
Additonal
setpoint
Caution:
Be aware, by changing of parameter P1000 all BICO parameters (see table below) are modified.
Note:
Single digits denote main setpoints that have no additional setpoint.
Changing this parameter sets (to default) all settings on item selected (see table).