Communication processor and Modbus TCP
13.3 Point-to-point (PtP) communication
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
1133
Table 13- 40 Data types for the parameters
REQ IN Bool Activate the configuration change on the rising edge of this input.
PORT IN PORT After you install and configure a CM or CB communication device,
the port identifier appears in the parameter helper drop-list available
at the PORT box connection. The assigned CM or CB port value is
the device configuration property "hardware identifier". The port sym-
bolic name is assigned in the "System constants" tab of the PLC tag
table. (Default value: 0)
EN_MODBUS_CRC IN Bool Enable MODBUS CRC generation and checking:
• 0: CRC calculation tuned OFF (default)
• 1: CRC calculation turned ON
Note: Only V2.1 CMs, V4.1 CPUs with CBs, and CM PtP modules for
distributed I/O support this parameter.
EN_DIAG_ALARM IN Bool Enable diagnostic alarm generation:
• 0: Diagnostic alarm turned OFF
• 1: Diagnostic alarm turned ON (default)
EN_SUPPLY_VOLT IN Bool Enable diagnostics for missing supply voltage L+:
• 0: Supply voltage diagnostic disabled (default)
• 1: Supply voltage diagnostic enabled
Indicates that set features is done
ERROR OUT Bool TRUE for one scan, after the last request was completed with an
Execution condition code (Default value: 0)