EasyManua.ls Logo

Siemens SIMATIC S7-1200

Siemens SIMATIC S7-1200
1614 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical specifications
A.10 Analog signal modules (SMs)
S7-1200 Programmable controller
1464 System Manual, V4.2, 09/2016, A5E02486680-AK
A.10.2
SM 1232 analog output module specifications
Table A- 145 General specifications
Technical data
SM 1232 AQ 2 x 14 bit
SM 1232 AQ 4 x 14 bit
Article number
6ES7232-4HB32-0XB0
6ES7232-4HD32-0XB0
Dimensions W x H x D (mm) 45 x 100 x 75
Weight
180 grams
Power dissipation 1.8 W 2.0 W
Current consumption (SM Bus)
80 mA
Current consumption (24 V DC)
45 mA (no load)
Table A- 146 Analog outputs
Technical data
SM 1232 AQ 2 x 14 bit
SM 1232 AQ 4 x 14 bit
Number of outputs
2
4
Type
Voltage or current
Range
±10 V, 0 to 20 mA, or 4 mA to 20 mA
Resolution Voltage: 14 bits
Current: 13 bits
Full scale range (data word) Voltage: -27,648 to 27,648 ; Current: 0 to 27,648
Refer to the output ranges for voltage and current (Page 1472).
Accuracy (25 °C / -20 to 60 °C)
±0.3% / ±0.6% of full scale
Settling time (95% of new value) Voltage: 300 μs (R), 750 μs (1 uF)
Current: 600 μs (1 mH), 2 ms (10 mH)
Load impedance Voltage: ≥ 1000 Ω
Current: ≤ 600 Ω
Maximum output short circuit current Voltage mode: ≤ 24 mA
Current mode: ≥ 38.5 mA
Behavior on RUN to STOP
Last value or substitute value (default value 0)
Isolation (field side to logic) none
Isolation (24 V to output)
none
Cable length (meters)
100 m twisted and shielded
Table A- 147 Diagnostics
Technical data
SM 1232 AQ 2 x 14 bit
SM 1232 AQ 4 x 14 bit
Overflow/underflow
Yes
Short to ground (voltage mode only) Yes
Wire break (current mode only)
Yes
24 V DC low voltage
Yes

Table of Contents