Communication processor and Modbus TCP
13.4 Universal serial interface (USS) communication
S7-1200 Programmable controller
1154 System Manual, V4.2, 09/2016, A5E02486680-AK
13.4.3.2
USS_Drive_Control (Swap data with drive)
Table 13- 44 USS_Drive_Control instruction
LAD / FBD
SCL
Description
"USS_Drive_Control_DB"(
RUN:=_bool_in_,
OFF2:=_bool_in_,
OFF3:=_bool_in_,
F_ACK:=_bool_in_,
DIR:=_bool_in_,
DRIVE:=_usint_in_,
PZD_LEN:=_usint_in_,
SPEED_SP:=_real_in_,
CTRL3:=_word_in_,
CTRL4:=_word_in_,
CTRL5:=_word_in_,
CTRL6:=_word_in_,
CTRL7:=_word_in_,
CTRL8:=_word_in_,
NDR=>_bool_out_,
ERROR=>_bool_out_,
STATUS=>_word_out_,
RUN_EN=>_bool_out_,
D_DIR=>_bool_out_,
INHIBIT=>_bool_out_,
FAULT=>_bool_out_,
SPEED=>_real_out_,
STATUS1=>_word_out_,
STATUS3=>_word_out_,
STATUS4=>_word_out_,
STATUS5=>_word_out_,
STATUS6=>_word_out_,
STATUS7=>_word_out_,
STATUS8=>_word_out_);
The USS_Drive_Control instruction exchanges data
with a drive by creating request messages and inter-
preting the drive response messages. A separate func-
tion block should be used for each drive, but all USS
functions associated with one USS network and PtP
communication port must use the same instance data
block. You must create the DB name when you place
the first USS_Drive_Control instruction and then refer-
ence the DB that was created by the initial instruction
usage.
STEP 7 automatically creates the DB when you insert
the instruction.
1
LAD and FBD: Expand the box to reveal all the parameters by clicking the bottom of the box. The parameter pins that
are grayed are optional and parameter assignment is not required.