Online and diagnostic tools
15.17 Backing up and restoring a CPU
S7-1200 Programmable controller
1352 System Manual, V4.2, 09/2016, A5E02486680-AK
15.17
Backing up and restoring a CPU
15.17.1
Backup and restore options
You will make a number of changes to your automation system over time, for example, add
new devices, replace existing devices or adapt the user program. If these changes were to
result in undesirable behavior, you can restore the automation plant to an earlier version if
you have a backup. STEP 7 and the S7-1200 CPU offer different options for backing up and
restoring the hardware configuration and software.
Backup options
The table below provides an overview of the backup and restoration options of S7 CPUs:
Snapshot of the moni-
tored values
Upload from device
(software)
Upload device as new
station (hardware and
software)
Download backup from
online device
Use case
Restoring a specific
status of a data block.
The actual values of
data blocks including
time stamp are ac-
cepted in the project.
Upload blocks from a
CPU to the project.
Upload of hardware
configuration and
software from a device
to the project.
Create a complete
backup of a CPU as a
restore point. The
backup copy is con-
sistent and cannot be
changed or opened.
Requirement
The CPU exists in a
project. The data
blocks must be identi-
cal online and offline.
The CPU exists in the
project.
The device is available
in the hardware cata-
log of TIA Portal. Any
necessary HSPs or
GSD files are installed.
-
Possible in mode
RUN, STOP
RUN, STOP
RUN, STOP
STOP
Possible for F-CPUs
Yes
Yes
No
Yes
Backup can be edited
Yes
Yes
Yes
No