Technical specifications
A.11 Thermocouple and RTD signal modules (SMs)
S7-1200 Programmable controller
1482 System Manual, V4.2, 09/2016, A5E02486680-AK
Selection tables for the SM 1231 RTD
Table A- 178 Ranges and accuracy for the different sensors supported by the RTD modules
Normal
range ac-
curacy
@ 25 °C
Normal range
accuracy
-20 °C to
60 °C
Pt 0.003850
ITS90
DIN EN 60751
Pt 100 climat-
-145.00 °C -120.00 °C 145.00 °C 155.00 °
±0.20 °C ±0.40 °C
Pt 10 -243.0 °C -200.0 °C 850.0 °C 1000.0 °
±1.0 °C ±2.0 °C
-243.0 °C -200.0 °C 850.0 °C 1000.0 °
C
±0.5 °C ±1.0 °C
Pt 0.003902
Pt 0.003916
Pt 0.003920
Pt 100 -243.0 °C -200.0 °C 850.0 °C 1000.0 °
± 0.5 °C ±1.0 °C
-243.0 °C -200.0 °C 850.0 °C 1000.0 °
C
± 0.5 °C ±1.0 °C
Pt 0.003910
-273.2 °C -240.0 °C 1100.0 °C 1295 °C ±0.8 °C ±1.6 °C
Ni 0.006720
Ni 0.006180
-105.0 °C -60.0 °C 250.0 °C 295.0 °C ±0.5 °C ±1.0 °C
LG-Ni 0.005000 LG-Ni 1000 -105.0 °C -60.0 °C 250.0 °C 295.0 °C ±0.5 °C ±1.0 °C
Cu 0.004260
-60.0 °C -50.0 °C 200.0 °C 240.0 °C ±0.6 °C ±1.2 °C
Cu 0.004280
-240.0 °C -200.0 °C 200.0 °C 240.0 °C ±0.7 °C ±1.4 °C
RTD values below the under-range minimum value report -32768.
2
RTD values above the over-range maximum value report +32767.