EasyManua.ls Logo

Siemens SIMATIC S7-1200

Siemens SIMATIC S7-1200
1614 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical specifications
A.16 Communication interfaces
S7-1200 Programmable controller
1544 System Manual, V4.2, 09/2016, A5E02486680-AK
Table A- 251 Power supply
Technical data
CM 1241 RS232
Power loss (dissipation)
1 W
From +5 V DC 200 mA
Table A- 252 RS232 connector (male)
Pin
Description
Connector
(male)
Pin
Description
1 DCD
Data carrier detect: Input
6 DSR
Data set ready: Input
2 RxD Received data from DCE: Input 7 RTS Request to send: Output
3 TxD
Transmitted data to DCE: Output
8 CTS
Clear to send: Input
4 DTR
Data terminal ready: Output
9 RI
Ring indicator (not used)
5 GND Logic ground SHELL Chassis ground
A.16.4.3
CM 1241 RS422/485 specifications
CM 1241 RS422/485 Specifications
Table A- 253 General specifications
Technical data
CM 1241 RS422/485
Article number
6ES7241-1CH32-0XB0
Dimensions W x H x H (mm)
30 x 100 x 75
Weight
155 grams
Table A- 254 Transmitter and receiver
Technical data
CM 1241 RS422/485
Type
RS422 or RS485, 9-pin sub D female connector
Common mode voltage range
-7 V to +12 V, 1 second, 3 VRMS continuous
Transmitter differential output voltage 2 V min. at R
L
= 100 Ω
1.5 V min. at R
L
= 54 Ω
Termination and bias 10K Ω to +5 V on B, PROFIBUS Pin 3
10K Ω to GND on A, PROFIBUS Pin 8
Internal bias options provided, or no internal bias. In all cases, exter-
nal termination is required, see Biasing and terminating an RS485
network connector (Page 1088) and Configuring the RS422 and
RS485 in the S7-1200 Programmable Controller System Manual
(Page 1140)
Receiver input impedance
5.4K Ω min. including termination
Receiver threshold/sensitivity +/- 0.2 V min., 60 mV typical hysteresis

Table of Contents

Other manuals for Siemens SIMATIC S7-1200

Related product manuals