Technical specifications
A.10 Analog signal modules (SMs)
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
1471
Measurement ranges of the analog inputs for voltage and current (SB and SM)
Table A- 159 Analog input representation for voltage (SB and SM)
1
Overflow
Overshoot range
27648 6C00 10 V 5 V 2.5 V 1.250 V Rated range
Undershoot range
Underflow
7FFF can be returned for one of the following reasons: overflow (as noted in this table), before valid values are available
(for example immediately upon a power up), or if a wire break is detected.
Table A- 160 Analog input representation for current (SB and SM)
Overshoot range
Nominal range
0 0 0 mA 4 mA
Undershoot range
-4864 ED00 -3.52 mA 1.185 mA
1
Underflow (0 to 20 mA)
1
The wire break value of 32767 (16#7FFF) is always returned regardless of the state of the wire break alarm.
Determining the type of wire break condition from an SM 1231 module (Page 1349)