EasyManua.ls Logo

Siemens SIMATIC S7-1200

Siemens SIMATIC S7-1200
1614 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Extended instructions
9.3 Distributed I/O (PROFINET, PROFIBUS, or AS-i)
S7-1200 Programmable controller
384 System Manual, V4.2, 09/2016, A5E02486680-AK
9.3
Distributed I/O (PROFINET, PROFIBUS, or AS-i)
9.3.1
Distributed I/O Instructions
The following Distributed I/O instructions can be used with PROFINET, PROFIBUS, or AS-i:
RDREC instruction (Page 385): Reads a data record with the number INDEX from a
module or device.
WRREC instruction (Page 385): Transfers a data record with the number INDEX to a
module or device defined by ID.
GETIO instruction (Page 388): Consistently reads out all inputs of a DP standard slave /
PROFINET IO device.
SETIO instruction (Page 389): Consistently transfers data from the source range defined
by the OUTPUTS parameter to the addressed DP standard slave / PROFINET IO device.
GETIO_PART instruction (Page 390): Consistently reads out a related part of the inputs
of an IO module.
SETIO_PART instruction (Page 392): Consistently writes data from the source area
spanned by the OUTPUTS parameter to the outputs of an IO module.
RALRM instruction (Page 394): Allows you to receive an interrupt with all corresponding
information from a module or device and supply this information to its output parameters.
DPRD_DAT instruction (Page 408): Allows you to read consistent data areas greater than
64 bytes from a module or device with the DPRD_DAT instruction.
DPWR_DAT instruction (Page 408): Allows you to write consistent data areas greater
than 64 bytes to a module or device with the DPWR_DAT instruction.
The D_ACT_DP instruction (Page 398) allows you to disable and enable configured
PROFINET IO devices in a targeted manner. You can also determine whether each
assigned PROFINET IO device is currently activated or deactivated.
Note
Note: You can only use the D_ACT_DP instruction with PROFINET IO devices. You cannot
use the instruction with PROFIBUS DP slaves.
The DPNRM_DG instruction (Page 416) allows you to read the current diagnostic data of a
DP slave in the format specified by EN 50 170 Volume 2, PROFIBUS.
Note
You can only use the DPNRM_D
G instruction with PROFIBUS.

Table of Contents

Other manuals for Siemens SIMATIC S7-1200

Related product manuals