Communication
11.2 PROFINET
S7-1200 Programmable controller
916 System Manual, V4.2, 09/2016, A5E02486680-AK
11.2.10
HMI-to-PLC communication
The CPU supports PROFINET communic
a-
tions connections to
HMIs (Page 32). The
fo
llowing requirements must be considered
when setting up communica
tions between
CPUs and HMIs:
Configuration/Setup:
The PROFINET port of the CPU must be configured to connect with the HMI.
The HMI must be setup and configured.
The HMI configuration information is part of the CPU project and can be configured and
downloaded from within the project.
No Ethernet switch is required for one-to-one communications; an Ethernet switch is
required for more than two devices in a network.
Note
The rack
-mounted CSM1277 4-port Ethernet switch can be used to connect your CPUs
and HMI devices. The PROFINET port on the CPU does not contain an Ethernet
switching device.
Supported functions:
The HMI can read/write data to the CPU.
Messages can be triggered, based upon information retrieved from the CPU.
System diagnostics