EasyManua.ls Logo

Siemens SIMATIC S7-1200 - Page 1211

Siemens SIMATIC S7-1200
1614 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communication processor and Modbus TCP
13.5 Modbus communication
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
1211
Extended_Addressing
The Extended_Addressing variable is accessed in a similar way as the HR_Start_Offset
reference discussed above except that the Extended_Addressing variable is a Boolean
value. The Boolean value must be written by an output coil and not a move box.
Modbus slave addressing can be configured to be either a single byte (which is the Modbus
standard) or double byte. Extended addressing is used to address more than 247 devices
within a single network. Selecting extended addressing allows you to address a maximum of
64000 addresses. A Modbus function 1 frame is shown below as an example.
Table 13- 87 Single-byte slave address (byte 0)
Function 1
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Request
Slave addr.
F code
Start address
Length of coils
Valid Response Slave addr. F code Length Coil data
Error response
Slave addr.
0x81
E code
Table 13- 88 Double-byte slave address (byte 0 and byte 1)
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Request Slave address F code Start address Length of coils
Valid Response
Slave address
F code
Length
Coil data
Error response
Slave address
0x81
E code

Table of Contents

Other manuals for Siemens SIMATIC S7-1200

Related product manuals