EasyManua.ls Logo

Siemens SIMATIC S7-1200 - Page 122

Siemens SIMATIC S7-1200
1614 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PLC concepts
5.2 Data storage, memory areas, I/O and addressing
S7-1200 Programmable controller
122 System Manual, V4.2, 09/2016, A5E02486680-AK
Note
When you specify an absolute address in LAD or FBD, STEP 7 precedes this address with a
"%" character to indicate that it is an absolute address.
While programming, you can enter
an absolute address either with or without the "%" character (for example %I0.0 or I.0). If
omitted, STEP
7 supplies the "%" character.
In SCL, you must enter the "%" before the address to indicate that it is an absolute a
ddress.
Without the "%", STEP
7 generates an undefined tag error at compile time
Configuring the I/O in the CPU and I/O modules
When you add a CPU and I/O modules to your
device configuration, STEP
7 automatically assigns
I and
Q addresses. You can change the default
addressing by selecting the address field in the
device configuration and entering new numbers.
STEP 7 assigns digital inputs and outputs in
groups of 8 points (1 byte), whether the module
uses all the points or not.
STEP 7 allocates analog inputs and outputs in
groups of 2, where each analog poing occupies
2 bytes (16 bits).
The figure shows an example of a CPU 1214C with two SMs and one SB. In this example,
you could change the address of the DI8 module to 2 instead of 8. The tool assists you by
changing address ranges that are the wrong size or conflict with other addresses.

Table of Contents

Other manuals for Siemens SIMATIC S7-1200

Related product manuals