Communication processor and Modbus TCP
13.8 Legacy Modbus TCP communication
S7-1200 Programmable controller
1254 System Manual, V4.2, 09/2016, A5E02486680-AK
Complex DB elements can be assigned by MB_DATA_PTR, such as
Standard arrays
Named structures where each element is unique.
Named complex structures where each element has a unique name and a 16 or 32 bit
data type.
There is no requirement that the MB_DATA_PTR data areas be in the same global data
block (or M memory area). You can assign one data block for Modbus reads, another
data block for Modbus writes, or one data block for each MB_CLIENT station.
Multiple client connections
A Modbus TCP client can support concurrent connections up to the maximum number of
Open User Communications connections allowed by the PLC. The total number of
connections for a PLC, including Modbus TCP Clients and Servers, must not exceed the
maximum number of supported Open User Communications connections (Page 801). The
Modbus TCP connections may be shared between Client and/or Server type connections.
Individual client connections must follow these rules:
Each MB_CLIENT connection must use a distinct instance DB
Each MB_CLIENT connection must specify a unique server IP address
Each MB_CLIENT connection must specify a unique connection ID
Unique IP port numbers may or may not be required depending upon the server
configuration
The Connection ID must be unique for each individual connection. This means a single,
unique Connection ID must only be used with each individual instance DB. In summary, the
instance DB and the Connection ID are paired together and must be unique for every
connection.