Technical specifications
A.11 Thermocouple and RTD signal modules (SMs)
S7-1200 Programmable controller
1484 System Manual, V4.2, 09/2016, A5E02486680-AK
Representation of Analog values for RTDs
A representation of the digitized measured value for the RTD standard temperature range
sensors are shown in the tables below.
Table A- 181 Representation of analog values for resistance thermometers PT 100, 200, 500, 1000
and PT 10, 50, 100, 500 GOST (0.003850) standard
Pt x00 stan-
dard in °C (1
digit =
0.1 °C)
Units
Pt x00 stan-
dard in °F (1
digit =
0.1 °F)
Units
Range
Decimal
Hexadecimal
Decimal
Hexadecimal
> 1000.0
32767
7FFF
> 1832.0
32767
7FFF
Overflow
1000.0
:
850.1
10000
:
8501
2710
:
2135
1832.0
:
1562.1
18320
:
15621
4790
:
3D05
Overrange
850.0
:
-200.0
8500
:
-2000
2134
:
F830
1562.0
:
-328.0
15620
:
-3280
3D04
:
F330
Rated range
-200.1
:
-243.0
-2001
:
-2430
F82F
:
F682
-328.1
:
-405.4
-3281
:
-4054
F32F
:
F02A
Underrange
< -243.0
-32768
8000
< -405.4
-32768
8000
Underflow

Table of Contents