EasyManua.ls Logo

Siemens SIMATIC S7-1200 - Page 1489

Siemens SIMATIC S7-1200
1614 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical specifications
A.12 Technology modules
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
1489
Properties
Technical properties
IO-Link Master according to IO-Link specification V1.1 (see the IO-Link Consortium
website (http://io-link.com/en/index.php) for details)
Serial communication module with four ports (channels)
Data transmission rate COM1 (4.8 kbaud), COM2 (38.4 kbaud), COM3 (230.4 kbaud)
SIO mode (standard IO mode)
Connection of up to four IO-Link devices (3-wire connection) or four standard actuators or
standard encoders
Programmable diagnostics function by port
Supported functions
I&M (installation and maintenance) identification data
Firmware update
IO-Link parameter assignment by means of the S7-PCT port configuration tool, STEP 7
Professional, and an S7-1200 V4.0 or later CPU
IO-Link is a point-to-point connection between a master and a device. Both conventional and
intelligent sensors/actuators can be used as devices at the IO-Link via unshielded standard
cables using proven 3-wire technology. IO-Link is backward compatible with conventional
digital sensors and actuators. The circuit state and data channel are designed in proven 24 V
DC technology.
For additional information about the SIMATIC-IO-Link technology, refer to the "IO-Link
system Function Manual" on the Siemens Industry Online Support website
(http://support.automation.siemens.com).
Note
IO-Link parameter data
When you replace the SM
4xIO-Link Master, the parameter data is not automatically
assigned to it.