Device exchange and spare parts compatibility
D.1 Exchanging a V3.0 CPU for a V4.2 CPU
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
1575
V3.0 CPU
(Motion control V3.0)
V4.2 CPU
(Motion control V5.0)
Config.Homing.SidePassiveHoming
Sensor[1].PassiveHoming.SideInput
Config.Homing.Offset Sensor[1].ActiveHoming.HomePositionOffset
Config.Homing.FastVelocity
Config.Homing.SlowVelocity
Homing.ReferencingVelocity
StatusPositioning.Distance
MotionStatus.TargetPosition
StatusPositioning.TargetPosition
StatusBits.VelocityCommand
The only "commandtable" parameter that is renamed is the array with the commands:
Note: The array "Command[]" is a UDT of the type "TO_CmdTab_Config_Command" in V3.0 and
"TO_Struct_Command" in V4.2.
The following instructions have changes in parameters or behavior:
● RDREC and WRREC (Page 385)
● CONV (Page 290)
If you had one or more HMI panels (Page 32) connected to your S7-1200 V3.0 CPU, the
communication to the S7-1200 V4.2 CPU depends on the type of communication you use
and the firmware version of the HMI panel. Recompile and download your project to the CPU
and the HMI and/or update your HMI firmware.