Extended instructions
9.3 Distributed I/O (PROFINET, PROFIBUS, or AS-i)
S7-1200 Programmable controller
402 System Manual, V4.2, 09/2016, A5E02486680-AK
80A6 Slot error in the PROFINET IO device; not all user data can be accessed (this error
code is only available when MODE = 1).
Note: D_ACT_DP returns this error information only if the activated component fails
again after parameter assignment and before the end of the D_ACT_DP instruction
execution. If only a single module is unavailable, D_ACT_DP returns the error infor-
80A7 A timeout occurred during activation: The remote device is unreachable, or you have
set the parameter assignment time for central and distributed I/O too short. The status
of the remote device is "activated", but it is not accessible.
Activation with errors in the PROFINET IO device: Differences in the configuration
Activation with errors in the PROFINET IO device: Parameter assignment error
Activation with errors in the PROFINET IO device: Maintenance required
80C1 D_ACT_DP has started and is being continued with another address (this error code
is possible when MODE = 1 and MODE = 2).
80C3
•
Temporary resource error: The CPU is currently processing the maximum possible
activation and deactivation jobs (8). (This error code is only possible when
MODE = 1 and MODE = 2.)
• The CPU is busy receiving a modified configuration. Currently, you cannot ena-
ble/disable PROFINET IO devices.
PROFINET: Jobs not collected by the user are discarded at restart.
General error
See the GET_ERROR_ID (Page 311) instruction for information on how to access the
* The error codes in the program editor can be displayed as integer or hexadecimal values.