Extended instructions
9.3 Distributed I/O (PROFINET, PROFIBUS, or AS-i)
S7-1200 Programmable controller
404 System Manual, V4.2, 09/2016, A5E02486680-AK
Table 9- 87 STATUS[3] values
Error_decode
(B#16#....)
Error_code_1
(B#16#....)
Explanation (DVP1)
Description
00
00
No error, no warning
70 00 Reserved, reject Initial call; no active data record transfer
01
Reserved, reject
Initial call; data record transfer has started
02
Reserved, reject
Intermediate call; data record transfer already active
80
90
Reserved, pass
Invalid logical start address
92
Reserved, pass
Illegal type for Variant pointer
93 Reserved, pass The DP component addressed via ID or F_ID is not con-
figured.
96 The "RALRM (Page 394)" cannot supply the OB start
information, management information, header infor-
mation, or additional interrupt information.
For the following OBs, you can use the "DPNRM_DG
(Page 416)" instruction to read the current diagnostics
message frame of the relevant DP slave asynchronously
(address information from OB start information):
Hardware interrupt (Page 95)
Status (Page 102), Update (Page 103) or Profile
(Page 103)
Diagnostic error interrupt (Page 97)
Pull or plug of modules (Page 100)
A0 Read error Negative acknowledgement while reading from the mod-
ule
A1
Write error
Negative acknowledgement while writing to the module
A2 Module failure DP protocol error at layer 2 (for example, slave failure or
bus problems)
A3 Reserved, pass
PROFIBUS DP: DP protocol error with Direct-Data-
Link-Mapper or User-Interface/User
PROFINET IO: General CM error
A4
Reserved, pass
Communication on the communication bus disrupted
A5
Reserved, pass
-
A7 Reserved, pass DP slave or modules is occupied (temporary error).
A8
Version conflict
DP slave or module reports non-compatible versions.
A9 Feature not supported Feature not supported by DP slave or module
AA to AF User specific DP slave or module reports a manufacturer-specific error
in its application. Please check the documentation from
the manufacturer of the DP slave or module.
B0 Invalid index Data record not known in module; illegal data record
number ≥ 256