9.5 Interrupts
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
421
Hardware interrupt events
The following hardware interrupt events are supported by the CPU:
Rising edge events: first 12 built-in CPU digital inputs (DIa.0 to DIb.3) and all SB digital
inputs
A rising edge occurs when the digital input transitions from OFF to ON as a response
to a change in the signal from a field device connected to the input.
Falling edge events: first 12 built-in CPU digital inputs (DIa.0 to DIb.3) and all SB digital
inputs
A falling edge occurs when the digital input transitions from ON to OFF.
High-speed counter (HSC) current value = reference value (CV = RV) events (HSC 1
through 6)
A CV = RV interrupt for a HSC is generated when the current count transitions from an
adjacent value to the value that exactly matches a reference value that was previously
established.
HSC direction changed events (HSC 1 through 6)
A direction changed event occurs when the HSC is detected to change from
increasing to decreasing, or from decreasing to increasing.
HSC external reset events (HSC 1 through 6)
Certain HSC modes allow the assignment of a digital input as an external reset that is
used to reset the HSC count value to zero. An external reset event occurs for such a
HSC, when this input transitions from OFF to ON.
Enabling hardware interrupt events in the device configuration
Hardware interrupts must be enabled during the device configuration. You must check the
enable-event box in the device configuration for a digital input channel or a HSC, if you want
to attach this event during configuration or run time.
Check box options within the PLC device configuration:
Digital input
Enable rising edge detection
Enable falling edge detection
High-speed counter (HSC)
Enable this high-speed counter for use
Generate interrupt for counter value equals reference value count
Generate interrupt for external reset event
Generate interrupt for direction change event