Extended instructions
9.8 Pulse
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
495
Table 9- 193 SB signal board output: Maximum frequency (PTO) and minimum cycle time (PWM)
SB signal board
SB output channel
PTO maximum fre-
quency
PWM minimum cycle
time
SB 1222, 200 kHz
DQe.0 to DQe.3
200kHz
5 µs
SB 1223, 200 kHz DQe.0, DQe.1 200kHz 5 µs
SB 1223
DQe.0, DQe.1
20 kHz
50 µs
Note
The minimum cycle time of each of the CPU and Signal Board outputs is given in the tables
above. However, TIA Portal does not alert you when you configure a PWM pulse generator
with
a cycle time that exceeds this hardware limitation. Problems can result with your
application, so always ensure that you do not exceed the minimum cycle time of the
hardware.
Parameter assignment
The Parameter assignment section allows the user to configure the parameters of the output
pulse. The following options are available, depending on whether PWM or PTO is selected:
Signal type: Configure the pulse output as PWM or PTO. For PTO selections, refer to
"Phasing" (Page 658) for further information:
PWM
PTO (pulse A and direction B)
PTO (pulse up A and pulse down B)
PTO (A/B phase-shifted)
PTO (A/B phase-shifted - fourfold)
Time base (only applies to PWM): Select which units of time to use:
Milliseconds
Microseconds
Pulse duration format (only applies to PWM): Assign the resolution of the pulse duration
(width):
Hundredths (0 to 100)
Thousandths (0 to 1000)
Ten-thousandths (0 to 10000)
S7 analog format (0 to 27648)
Cycle time (only applies to PWM): Assign the time duration it takes to complete one pulse
(pulse high time plus pulse low time equals cycle time). You can change the cycle time at
runtime by selecting the check box "Allow runtime modification of the cycle time". Refer to
the "I/O addresses" section below for further information. Range is 1 to 16,777,215 units
of time.