EasyManua.ls Logo

Siemens SIMATIC S7-1200 - Page 594

Siemens SIMATIC S7-1200
1614 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technology instructions
10.2 PID control
S7-1200 Programmable controller
594 System Manual, V4.2, 09/2016, A5E02486680-AK
Parameter and type
Data type
Description
Output_PWM
1
OUT Bool Output value for pulse width modulation. (Default value: FALSE)
On and Off times form the output value.
SetpointLimit_H OUT Bool Setpoint high limit. (Default value: FALSE)
If SetpointLimit_H = TRUE, the absolute setpoint upper limit is reached
(Setpoint ≥ Config.SetpointUpperLimit).
The setpoint is limited to Config.SetpointUpperLimit.
SetpointLimit_L OUT Bool Setpoint low limit. (Default value: FALSE)
If SetpointLimit_L = TRUE, the absolute setpoint lower limit is reached
(Setpoint ≤ Config.SetpointLowerLimit).
The setpoint is limited to Config.SetpointLowerLimit.
InputWarning_H OUT Bool If InputWarning_H = TRUE, the process value has reached or exceed-
ed the warning high limit. (Default value: FALSE)
InputWarning_L OUT Bool If InputWarning_L = TRUE, the process value has reached or fallen
below the warning low limit. (Default value: FALSE)
State OUT Int Current operating mode of the PID controller. (Default value: 0)
You can change the operating mode using the Mode input parameter
and a rising edge at ModeActivate:
State = 0: Inactive
State = 1: Pre-tuning
State = 2: Manual fine tuning
State = 3: Automatic mode
State = 4: Manual mode
State = 5: Substitute output value with error monitoring
Error OUT Bool If Error = TRUE, at least one error message is pending in this cycle.
(Default value: FALSE)
Note: The Error parameter in V1.x PID was the ErrorBits field that con-
tained the error codes. It is now a Boolean flag indicating that an error
has occurred.
ErrorBits OUT DWord The PID_Compact instruction ErrorBits parameters table (Page 597)
defines the error messages that are pending. (Default value:
DW#16#0000 (no error)). ErrorBits is retentive and is reset upon a
rising edge at Reset or ErrorAck.
Note: In V1.x, the ErrorBits parameter was defined as the Error param-
eter and did not exist.
1
You can use the outputs of the Output, Output_PER, and Output_PWM parameters in parallel.

Table of Contents

Other manuals for Siemens SIMATIC S7-1200

Related product manuals