Communication
11.2 PROFINET
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
847
ERROR
STATUS
(W#16#...)
Description
1 8085
The LEN parameter is larger than the highest permitted value.
The value at the LEN or DATA parameter was changed after the first call.
1
8086
The ID parameter within the CONNECT parameter is outside the permitted range.
1
8087
Maximum number of connections reached; no additional connection possible.
1 8088 The value at the LEN parameter does not correspond to the receive area set at the DATA
parameter.
1
8089
The CONNECT parameter does not point to a data block.
1
8091
Maximum nesting depth exceeded.
1 809A The CONNECT parameter points to a field that does not correspond to the length of the con-
nection description.
1
809B
The ID of the local device in the connection description does not correspond to the CPU.
1 80C3
All connection (Page 828) resources are in use.
A block with this ID is already being processed in a different priority group.
1 80C4 Temporary communication error:
The connection cannot be established at this time.
The interface is receiving new parameters or the connection is being established.
The configured connection is being removed by a "TDISCON (Page 857)" instruction.
The connection used is being terminated by a call with COM_RST = 1.
1
8722
Error in the CONNECT parameter: Invalid source area (area not declared in data block).
1 873A Error in the CONNECT parameter: Access to connection description is not possible (no access
to data block).
1
877F
Error in the CONNECT parameter: Internal error
1
8822
TSEND_C: DATA parameter: Invalid source area, the area does not exist in the DB.
1
8824
TSEND_C: DATA parameter: Area error in the VARIANT pointer.
1
8832
TSEND_C: DATA parameter: The DB number is too high.
1 883A TSEND_C: CONNECT parameter: Access to specified connection data not possible (for ex-
ample, because the DB does not exist).
1
887F
TSEND_C: DATA parameter: Internal error (for example, invalid VARIANT reference)
1 893A TSEND_C: DATA parameter: Access to send area not possible (for example, because the DB
does not exist).
1
8922
TRCV_C: DATA parameter: Invalid target area; the area does not exist in the DB.
1
8924
TRCV_C: DATA parameter: Area error in the VARIANT pointer.
1
8932
TRCV_C: DATA parameter: The DB number is too high.
1 893A TRCV_C: CONNECT parameter: Access to specified connection data not possible (for exam-
ple, because the DB does not exist).
1
897F
TRCV_C: DATA parameter: Internal error (for example, invalid VARIANT reference).
1 8A3A TRCV_C: DATA parameter: No access to the data area (for example because the data block
does not exist).