Communication
11.2 PROFINET
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
855
ERROR
STATUS
Description
1 80A1 Communications error:
The specified connection was not yet established
The specified connection is currently being terminated; transmission over this con-
nection is not possible
The interface is being reinitialized
1 80A3 Attempt being made to terminate a nonexistent connection
1 80A4 IP address of the remote partner connection is invalid. For example, the remote partner
IP address is the same as the local partner IP address.
1 80A5 Connection ID (Page 828) is already in use.
1
80A7
Communications error: You called TDISCON before TSEND_C was complete.
1 80B2 The CONNECT parameter points to a data block that was generated with the keyword
UNLINKED.
1 80B3 Inconsistent parameters:
Error in the connection description
Local port (parameter local_tsap_id) is already present in another connection de-
scription.
ID in the connection description different from the ID specified as parameter
1 80B4 When using the ISO on TCP (connection_type = B#16#12) to establish a passive con-
nection, condition code 80B4 alerts you that the TSAP entered did not conform to one
of the following address requirements:
For a local TSAP length of 2 and a TSAP ID value of either E0 or E1 (hexadecimal)
for the first byte, the second byte must be either 00 or 01.
For a local TSAP length of 3 or greater and a TSAP ID value of either E0 or E1
(hexadecimal) for the first byte, the second byte must be either 00 or 01 and all oth-
er bytes must be valid ASCII characters.
For a local TSAP length of 3 or greater and the first byte of the TSAP ID does not
have a value of either E0 or E1 (hexadecimal), then all bytes of the TSAP ID must
be valid ASCII characters.
Valid ASCII characters are byte values from 20 to 7E (hexadecimal).
1 80B7 Data type and/or length of the transmitted data does not fit in the area in the partner
CPU in which it is to be written.
1
80C3
All connection resources are in use.
1 80C4 Temporary communications error:
The connection cannot be established at this time
The interface is receiving new parameters
The configured connection is currently being removed by a TDISCON.
1
8722
CONNECT parameter: Source area invalid: area does not exist in DB.
1 873A CONNECT parameter: Access to connection description is not possible (for example,
DB not available)
1
877F
CONNECT parameter: Internal error such as an invalid ANY reference
1
893A
Parameter contains the number of a DB that is not loaded.