Communication
11.2 PROFINET
S7-1200 Programmable controller
882 System Manual, V4.2, 09/2016, A5E02486680-AK
STATUS parameter
The following table shows the meaning of the values at the STATUS parameter:
Error bit
STATUS*
(W#16#...)
Description
0 0000 The instruction "T_DIAG" has been executed successfully. The data in the structure referenced at
the RESULT parameter can be evaluated.
0 7000 No instruction processing active.
0
7001
Instruction processing launched.
0 7002 Connection information is being read (REQ parameter irrelevant).
1
8086
The value at the ID parameter is outside the valid range (W#16#0001 ... W#16#0FFF).
1 8089 The RESULT parameter points to an invalid data type (structures TDIAG_Status and
TDIAG_StatusExt only).
1 80A3 The ID parameter references a connection end point which does not exist. With programmed
connections, this error can also occur after the "TDISCON" instruction is called.
1
80C4
Internal error. Access to the connection end point is temporarily unavailable.