EasyManua.ls Logo

Siemens SIMATIC S7-1200 - Page 946

Siemens SIMATIC S7-1200
1614 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communication
11.2 PROFINET
S7-1200 Programmable controller
946 System Manual, V4.2, 09/2016, A5E02486680-AK
I-device
You assign the following parameters for an S7-1200 CPU as an I-device:
Centralized and distributed I/O
Desired transfer areas
Number of IO controllers having access to this I-device (always greater than 1 for a
shared device)
Note
You configure the I
-device without a higher-level IO controller. As a result, you can only use
the local I/O addresses of the transfer area (corresponds with the "Address in the I
-device")
to create the user program for editing the addresses from the transfer area. You download
the I
-device, completely configured except for the connection to the higher-level IO
controller, to the S7
-1200 CPU.
You export a PROFINET GSD file from the I-device configuration.
Controllers that share the I-device
You must install the PROFINET GSD file created from the I-device configuration in all
engineering systems that you use in configuring a PROFINET IO system with this shared
I-device. If you configure all uses of this I-device with STEP 7 V13 SP1, it is sufficient to
install the GSD file in STEP 7.
You configure the I-device as a GSD variant on the PROFINET IO system in the projects
involved. In STEP 7 V13 SP1, you find this I-device under "Other field devices > PROFINET
IO > PLCs & CPs" following installation.
In each of the projects involved, you assign transfer areas exclusively to the higher-level IO
controllers (default setting: all). You set the other transfer areas to "---" (not assigned). When
you do so, the local IO controller cannot access this transfer area, and you can assign the
transfer area to another IO controller in another project.
Requirements
STEP 7 V13 SP1 or higher
IO device supports shared device functionality (for example, ET 200SP IM 155-6 PN HF
V3.1).
GSD file for configuring the IO device as a shared device is installed.

Table of Contents

Other manuals for Siemens SIMATIC S7-1200

Related product manuals