6 Wiring
6.4.7 Operating Conditions on 400-V Power Supply Voltage
6-28
6.4.7 Operating Conditions on 400-V Power Supply Voltage
There are four types of SGDM SERVOPACKs, for the power supply voltages: Single-phase 100 VAC, single-
phase 200 VAC, and three-phase 200 VAC. When using the SERVOPACK for 100 V or 200 V with the three-
phase 400-VAC class (380 to 480 V), prepare the following voltage conversion transformers (single-phase or
three-phase)
When selecting a voltage conversion transformer, refer to the capacities shown in the following table.
* This is the net value at the rated load.
Single-phase Power Supply Connection Example
• Do not connect the SERVOPACK for 100 V and 200 V directly to a voltage of 400 V.
The SERVOPACK will be destroyed.
• Control the AC power supply ON and OFF sequence at the primary side of voltage conversion transfer.
Voltage conversion transfer inductance will cause a surge voltage if the power is turned ON and OFF at the secondary,
damaging the SERVOPACK.
Primary Voltage Secondary Voltage
380 to 480 VAC
380 to 480 VAC
→
→
200 VAC
100 VAC
Voltage
SERVOPACK Model
SGDM-
Voltage Capacity per
SERVOPACK * (kVA)
Current Capacity of Circuit
Breaker or Fuse (A
rms
)
Single-phase
100 V
A3BD, A3BDA 0.15
4A5BD, A5BDA 0.25
01BD, 01BDA 0.40
02BD, 02BDA 0.60 6
Single-phase
200 V
A3AD, A3ADA 0.20
4
A5AD, A5ADA 0.25
01AD, 01ADA 0.40
02AD, 02ADA 0.75
04AD, 04ADA 1.2 8
Three-phase
200 V
05AD, 05ADA 1.4 4
08AD, 08ADA 1.9
7
10AD, 10ADA 2.3
15AD, 15ADA 3.2 10
20AD, 20ADA 4.3 13
30AD, 30ADA 5.9 17
50ADA 7.5 28
60ADA 12.5 32
75ADA 15.5 41
1AADA 22.7 60
1EADA 30.9 81
Single-phase
Magnetic contactor for
power supply ON and OFF
Voltage conversion
transformer
100 or 200 VAC
SERVOPACK
R
S
T
1KM
1KM
L1
L2