EasyManua.ls Logo

YASKAWA V1000 Series

YASKAWA V1000 Series
372 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
n
Input Voltage Setting Value: E1-01
The input voltage level determines the overvoltage detection level and the operation level of the braking transistor as shown in the table below.
Voltage Setting Value of E1-01
(Approximate Values)
OV Detection
Level
Braking Transistor
Operation Level
UV Detection Level
Desired AC Voltage
during KEB
Voltage Level for OV
Suppression, Stall
Prevention
200 V Class all settings 410 V 394 V
190 V
(single-phase=160 V)
240 V 370 V
400 V Class
setting ≥ 400V 820 V 788 V 380 V 480 V 740 V
setting < 400V 740 V 708 V 350 V 440 V 660 V
Note: This data is for an internal dynamic braking resistor of 0.1 to 18.5 kW. For larger units, see “Dynamic Braking Resistor Unit for VARISPEED-600 Series, TOBPC72060000.”
u
V/f Pattern Selection: E1-03
Parameter E1-03 is only available when using V/f Control. It allows the user to set the required V/f pattern and drive output voltage. When running a
high-speed or special-purpose motor, this function fine tunes the amount of torque required for the load. Select the V/f pattern from 15 fixed V/f patterns
or 1 user-programmable V/f pattern.
No. Parameter Name Description Setting Range Default
E1-03 V/f Pattern Selection
0 to E: Select from 15 preset V/f patterns.
F: Custom V/f pattern (allows use of E1-04 through E1-10).
0 to F F
n
Setting Instructions for Setting a V/f Pattern
1.
Set the input voltage for the drive.
Refer to Drive Input Voltage Setting: E1-01 on page 83.
2.
Select one of the two following V/f patterns:
• *Select one of the 15 preset V/f patterns (setting = 0 through E)
• **Select the Custom V/f pattern (setting = F)
3.
In case of *, the following parameters are automatically set.
In case of **, the following parameters are adjustable.
E1-04 (Max Output Frequency), E1-05 (Max Voltage), E1-06 (Base Frequency), E1-07 (Mid Output Frequency), E1-08 (Mid Output Frequency
Voltage), E1-09 (Min Output Frequency), E1-10 (Min Output Frequency Voltage)
Output Voltage (V)
Frequency (Hz)
E1-05
E1-12
E1-13
E1-08
E1-10
E1-09 E1-07 E1-06 E1-11 E1-04
Figure 4.24 V/f Pattern
n
Selecting a Preset V/f Pattern
There are two types of V/f patterns: a method to select one of the 15 presets (set value: 0 to E) and a method to select arbitrary V/f pattern (set value: F).
Refer to
Table 4.20 .
No. Parameter Name
E1-04 Maximum Output Frequency (FMAX)
E1-05 Maximum Voltage (VMAX)
E1-06 Base Frequency (FA)
E1-07 Mid Output Frequency (FB)
No. Parameter Name
E1-08 Mid Output Frequency Voltage (VC)
E1-09 Minimum Output Frequency (FMIN)
E1-10 Minimum Output Frequency Voltage (VMIN)
Note: The default setting for the V/f pattern is for a custom V/f pattern (E1-03 = F).
Table 4.20 V/f Patterns
Setting Specification Characteristic Application
0 50 Hz
Constant torque
For general purpose applications, torque remains constant regardless of speed
changes.
1 (F) 60 Hz
2 60 Hz (with 50 Hz base)
3 72 Hz (with 60 Hz base)
4 50 Hz, Heavy Duty 3
Reduced or variable torque
For applications where torque changes with the speed like fans, pumps, and
others that require reduced torque relative to the load.
5 50 Hz, Heavy Duty 2
6 60 Hz, Heavy Duty 3
7 60 Hz, Heavy Duty 2
8 50 Hz, mid starting torque
High starting torque
High starting should be selected only when:
Wiring between the drive and motor exceeds 150 m
Large amount of starting torque is required
AC reactor is installed
motor exceeds the largest motor recommended for that drive used
9 50 Hz, high starting torque
A 60 Hz, mid starting torque
B 60 Hz, high starting torque
4.6 Basic Drive Setup Adjustments
84
YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)

Table of Contents

Other manuals for YASKAWA V1000 Series

Related product manuals