EasyManuals Logo

YASKAWA V1000 Series Technical Manual

YASKAWA V1000 Series
372 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #304 background imageLoading...
Page #304 background image
No. Name Description Range Def.
Control Mode
Addr. Hex Pg.
V/f
OL
V
PM
E5-07 <25> Motor q Axis Inductance Sets the q axis inductance in units of 0.01 mH. 0.00 to 600.00 <10> S 32F 325
E5-09 <25>
Motor Induction Voltage
Constant 1
Set the induced phase peak voltage in units of 0.1 mV (rad/min) [electrical
angle].
Set this parameter when using a Yaskawa SSR1 series PM motor with derate
torque, or a Yaskawa SST4 series motor with constant torque.
When setting this parameter, E5-24 should be set to 0. An alarm will be
triggered if both E5-09 and E5-24 are set to 0, or if neither parameter is set to
0.
0.0 to 2000.0 <10> S 331 325
E5-24 <25> Motor Induction Voltage
Parameter 2
Set the induced phase-to-phase rms voltage in units of 0.1 mV/(r/min)
[mechanical angle].Set this parameter when using a Yaskawa SMRA series
pico motor.
When setting this parameter, E5-09 should be set to 0. An alarm will be
triggered if both E5-09 and E5-24 are set to 0, or if neither parameter is set to
0.
If E5-03 (Motor Rated Current) is set to 0, however, then an alarm will not be
triggered when both E5-09 and E5-24 are set to 0.
0.0 to 2000.0 0 <10> S 353 325
Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 = 2-OLV control.
Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 = 0-V/f Control.
Default setting value is dependent on parameter A1-06. This setting value is 0 when A1-06 = 0, and 1 when A1-06 does not = 0.
Default setting value is dependent on parameter E5-01, Motor Code Selection.
Default setting value is dependent on parameter o2-04, Drive/kVA Selection.
Default setting value is dependent on parameter o2-04, Drive Capacity, when parameter H1-oo = 16 Motor 2 is selected as a digital input. The value shown is when o2-04 = 98 (62H) 200V
class 0.4 kW drive.
Range upper limit is dependent on parameters E5-01, Motor Code Selection, and A1-02, Control Method Selection. The value shown is for A1-02 = 5-PM OLV control.
Range upper limit is dependent on parameter E4-01 Motor 2 Rated Current.
Parameter can be changed during run.
Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
Parameter setting value is not reset to the default value during drive initialization, A1-03 = 1110, 2220, 3330.
Parameter ignored when E1-11, Motor 1 Mid Output Frequency 2, and E1-12, Motor 1 Mid Output Frequency Voltage 2, are set to 0.0.
Setting units for this parameter are determined by o2-04, Drive/kVA Selection. Less than 11 kW: 2 decimal points, 11 kW and above: 1 decimal point.
When parameter A1-02 = 5-PM OLV Control, E3-13 Motor 2 Base Voltage will be equal to T1-03, Motor Rated Voltage, after Auto-Tuning the drive
Default setting is determined by the V/f pattern selected to parameter E1-03.
Default setting changes when using OLV Control for PM motors.
Setting range becomes 0.00 to 130.00 for drives 0.2 kW and smaller.
If using a Yaskawa pico motor, the default setting is 1800 r/min.
Parameter ignored when E3-11, Motor 2 Mid Output Frequency 2, and E3-12, Motor 2 Mid Output Frequency Voltage 2, are set to 0.
Default setting depends on the control mode for motor 2 set in parameter E3-01. The given value is for V/f control.
Default setting value is dependent on parameter o2-04, Drive/kVA Selection and C6-01, Drive Duty Selection.
u
F: Options
F parameters are used to program the drive for PG feedback and to function with option cards.
No. Name Description Range Def.
Control Mode
Addr.
Hex
Pg.
V/f
OL
V
PM
F1: Simple PG V/f Parameters
Use F1 parameters to set up the drive for Simple PG V/f control. These parameters are enabled only when H6-01 = 03.
F1-02
Operation Selection at PG Open Circuit
(PGO)
Sets stopping method when a PG open circuit fault (PGO) occurs. Refer to
parameter F1-14.
0: Ramp to Stop - Decelerate to stop using the active deceleration time.
1: Coast to Stop
2: Fast-stop - Decelerate to stop using the deceleration time in C1-09.
3: Alarm only - Drive continues operation.
0 to 3 1 A 381
F1-03
Operation Selection at Overspeed
(OS)
Sets the stopping method when an overspeed (OS) fault occurs. Refer to F1-08
and F1-09.
0: Ramp to stop - Decelerate to stop using the active deceleration time.
1: Coast to stop
2: Fast - Stop - Decelerate to stop using the deceleration time in C1-09.
3: Alarm Only - Drive continues operation.
0 to 3 1 A 382
F1-04 Operation Selection at Deviation
Sets the stopping method when a speed deviation (DEV) fault occurs. Refer to
F1-10 and F1-11.
0: Ramp to stop - Decelerate to stop using the active deceleration time.
1: Coast to stop
2: Fast-stop - Decelerate to stop using the deceleration time in C1-09.
3: Alarm only - Drive continues operation.
0 to 3 3 A 383
F1-08 Overspeed Detection Level
Sets the speed feedback level which has to be exceeded for the time set in F1-09
before an OS fault will occur.
Set as a percentage of the maximum output frequency (E1-04).
0 to 120 115% A 387
F1-09 Overspeed Detection Delay Time
Sets the time in seconds for which the speed feedback has to exceed the overspeed
detection level F1-08 before an OS fault will occur.
0.0 to 2.0 1.0 A 388
F1-10
Excessive Speed Deviation Detection
Level
Sets the allowable deviation between motor speed and frequency reference before
a speed deviation fault (DEV) is triggered.
Set as a percentage of the maximum output frequency (E1-04).
0 to 50 10% A 389
F1-11
Excessive Speed Deviation Detection
Delay Time
Sets the time in seconds for which a deviation between motor speed and
frequency reference has to exceed the speed deviation detection level F1-10
before a DEV fault will occur.
0.0 to 10.0 0.5 s A 38A
F1-14 PG Open-Circuit Detection Time
Sets the time for which no PG pulses must be detected before a PG Open (PGO)
fault is triggered.
0.0 to 10.0 2.0 s A 38D
B.2 Parameter Table
304
YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)

Table of Contents

Other manuals for YASKAWA V1000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA V1000 Series and is the answer not in the manual?

YASKAWA V1000 Series Specifications

General IconGeneral
ModelV1000 Series
SeriesV1000
Output Frequency0.1 to 400 Hz
Overload Capacity150% for 60 seconds
TypeAC Drive
Control MethodV/f Control
Input Voltage200-240V, 380-480V
Output Voltage0 to Input Voltage
Power Range0.1 to 18.5 kW
Horsepower0.2 to 25 HP
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit, Ground Fault
Communication InterfacesModbus RTU
EnclosureIP20
Ambient Temperature-10 to +50°C
Storage Temperature-20 to +60°C
Humidity5 to 95% RH (non-condensing)
Cooling MethodFan Cooled

Related product manuals