Measuring mode for phase current and residual current values can be selected with the
Measurement mode setting parameter.
3.8.3 Settings
Table 44: FLR settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
Trig mode 0=Trip or Pickup
1=Trip only
2=Pickup only
0=Trip or Pickup Triggering mode
Table 45: FLR settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Measurement mode 1=RMS
2=DFT
3=Peak-to-Peak
2=DFT Selects used measurement mode
Section 3 1MAC059074-MB A
Basic functions
94 615 series ANSI
Technical Manual