6.1.7 Settings
Table 736: TCM Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
Trip delay time 20...300000 ms 1 3000 Trip delay time
Table 737: TCM Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 20...60000 ms 1 1000 Reset delay time
6.1.8 Monitored data
Table 738: TCM Monitored data
Name Type Values (Range) Unit Description
TCM Enum 1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
6.1.9 Technical revision history
Table 739: TCM Technical revision history
Technical revision
Change
B Internal improvement
C Internal improvement
6.2 Current circuit supervision CCM
6.2.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Current circuit supervision CCSPVC MCS 3I CCM
1MAC059074-MB A Section 6
Supervision functions
615 series ANSI 845
Technical Manual