EasyManua.ls Logo

ABB 615 Series - Technical Data

ABB 615 Series
1196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Name Type Values (Range) Unit Description
I_DB_A FLOAT32 0.00...40.00 xIn IA Amplitude, magnitude of
reported value
I_DMD_A FLOAT32 0.00...40.00 xIn Demand value of IA current
I_RANGE_A Enum 0=normal
1=high
2=low
3=high-high
4=low-low
IA Amplitude range
I_INST_B FLOAT32 0.00...40.00 xIn IB Amplitude, magnitude of
instantaneous value
I_ANGL_B FLOAT32 -180.00...180.00 deg IB current angle
I_DB_B FLOAT32 0.00...40.00 xIn IB Amplitude, magnitude of
reported value
I_DMD_B FLOAT32 0.00...40.00 xIn Demand value of IB current
I_RANGE_B Enum 0=normal
1=high
2=low
3=high-high
4=low-low
IB Amplitude range
I_INST_C FLOAT32 0.00...40.00 xIn IC Amplitude, magnitude of
instantaneous value
I_ANGL_C FLOAT32 -180.00...180.00 deg IC current angle
I_DB_C FLOAT32 0.00...40.00 xIn IC Amplitude, magnitude of
reported value
I_DMD_C FLOAT32 0.00...40.00 xIn Demand value of IC current
I_RANGE_C Enum 0=normal
1=high
2=low
3=high-high
4=low-low
IC Amplitude range
8.1.4.6 Technical data
Table 799: IA, IB, IC Technical data
Characteristic
Value
Operation accuracy Depending on the frequency of the measured
current: f
n
±2 Hz
±0.5% or ±0.002 × I
n
(at currents in the range of 0.01...4.00 × I
n
)
Suppression of harmonics DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
RMS: No suppression
1MAC059074-MB A Section 8
Measurement functions
615 series ANSI 909
Technical Manual

Table of Contents