Table 419: 67YN Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
Operation mode 1=Intermittent EF
3=General EF
4=Alarming EF
3=General EF Operation criteria
Table 420: 67YN Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
IG/I0 signal Sel 1=Measured IG
2=Calculated I0
1=Measured IG Measured IG or calculated I0
Vg or V0 1=Measured VG
2=Calculated V0
1=Measured VG Selection for used Uo signal
Peak counter limit 2...20 1 2 Peak counter limit for restriking EF
Pickup delay time 30...60000 ms 1 30 Pickup delay time
Reset delay time 0...60000 ms 1 500 Reset delay time
Pol reversal 0=False
1=True
0=False Rotate polarizing quantity
4.2.8.8 Monitored data
Table 421: 67YN Monitored data
Name
Type Values (Range) Unit Description
PICKUP_DUR FLOAT32 0.00...100.00 % Ratio of pickup time / trip time
FAULT_DIR Enum 0=unknown
1=forward
2=backward
3=both
Detected fault direction
DIRECTION Enum 0=unknown
1=forward
2=backward
3=both
Direction information
ANGLE FLOAT32 -180.00...180.00 deg Angle between operating
angle and characteristic angle
67YN Enum 1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status