Name Type Description
CMD_FAIL_AL BOOLEAN CB closing request failed
LLDB BOOLEAN Live Line, Dead Bus
LLLB BOOLEAN Live Line, Live Bus
DLLB BOOLEAN Dead Line, Live Bus
DLDB BOOLEAN Dead Line, Dead Bus
9.3.7 Settings
Table 897: 25 Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Live dead mode -1=Disable
1=Both Dead
2=Live L, Dead B
3=Dead L, Live B
4=Dead Bus, L Any
5=Dead L, Bus Any
6=One Live, Dead
7=Not Both Live
1=Both Dead Energizing check mode
Difference voltage 0.01...0.50 xUn 0.01 0.05 Maximum voltage difference limit
Difference frequency 0.001...0.100 xFn 0.001 0.001 Maximum frequency difference limit
Difference angle 5...90 deg 1 5 Maximum angle difference limit
Table 898: 25 Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
Synchro check mode 1=Disable
2=Synchronous
3=Asynchronous
3=Asynchronous Synchro check operation mode
Dead line value 0.1...0.8 xUn 0.1 0.2 Voltage low limit line for energizing check
Live line value 0.2...1.0 xUn 0.1 0.8 Voltage high limit line for energizing check
Dead bus value 0.1...0.8 xUn 0.1 0.2 Voltage low limit bus for energizing check
Live bus value 0.2...1.0 xUn 0.1 0.5 Voltage high limit bus for energizing check
Max energizing V 0.50...1.15 xUn 0.01 1.05 Maximum voltage for energizing