3.5.1.4 Settings
Table 29: Time format
Parameter
Values (Range) Unit Step Default Description
Time format 1=24H:MM:SS:MS
2=12H:MM:SS:MS
1=24H:MM:SS:M
S
Time format
Date format 1=DD.MM.YYYY
2=DD/MM/YYYY
3=DD-MM-YYYY
4=MM.DD.YYYY
5=MM/DD/YYYY
6=YYYY-MM-DD
7=YYYY-DD-MM
8=YYYY/DD/MM
1=DD.MM.YYYY Date format
Table 30: Time settings
Parameter Values (Range) Unit Step Default Description
Synch source 0=None
1=SNTP
2=Modbus
3=IEEE 1588
5=IRIG-B
9=DNP
1=SNTP Time synchronization source
PTP domain ID 0...255 1 0 The domain is identified by an integer, the
domainNumber, in the range of 0 to 255.
PTP priority 1 0...255 1 128 PTP priority 1, in the range of 0 to 255.
PTP priority 2 0...255 1 128 PTP priority 2, in the range of 0 to 255.
PTP announce mode 1=Basic IEEE1588
2=Power Profile
1=Basic IEEE1588 PTP announce frame mode
Table 31: Time settings
Parameter
Values (Range) Unit Step Default Description
Date 0 Date
Time 0 Time
Local time offset -840...840 min 1 0 Local time offset in minutes
Table 32: Time settings
Parameter
Values (Range) Unit Step Default Description
IP SNTP primary 10.58.125.165 IP address for SNTP primary server
IP SNTP secondary 192.168.2.165 IP address for SNTP secondary server
1MAC059074-MB A Section 3
Basic functions
615 series ANSI 85
Technical Manual