4.7.2.8 Monitored data
Table 611: 40 Monitored data
Name
Type Values (Range) Unit Description
PICKUP_DUR FLOAT32 0.00...100.00 % Ratio of pickup time / trip time
(in %)
Z_AMPL_A FLOAT32 0.00...200.00 xZn Impedance amplitude phase A
Z_ANGLE_A FLOAT32 -180.00...180.00 deg Impedance angle phase A
Z_AMPL_B FLOAT32 0.00...200.00 xZn Impedance amplitude phase B
Z_ANGLE_B FLOAT32 -180.00...180.00 deg Impedance angle phase B
Z_AMPL_C FLOAT32 0.00...200.00 xZn Impedance amplitude phase
C
Z_ANGLE_C FLOAT32 -180.00...180.00 deg Impedance angle phase C
Z_AMPL_AB FLOAT32 0.00...200.00 xZn Phase-to-phase A-B
impedance amplitude
Z_ANGLE_AB FLOAT32 -180.00...180.00 deg Phase-to-phase A-B
impedance phase angle
Z_AMPL_BC FLOAT32 0.00...200.00 xZn Phase-to-phase B-C
impedance amplitude
Z_ANGLE_BC FLOAT32 -180.00...180.00 deg Phase-to-phase B-C
impedance phase angle
Z_AMPL_CA FLOAT32 0.00...200.00 xZn Phase-to-phase C-A
impedance amplitude
Z_ANGLE_CA FLOAT32 -180.00...180.00 deg Phase-to-phase C-A
impedance phase angle
Z1_AMPL FLOAT32 0.00...200.00 xZn Positive sequence impedance
amplitude
Z1_ANGLE FLOAT32 -180.00...180.00 deg Positive sequence impedance
phase angle
40 Enum 1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
1MAC059074-MB A Section 4
Protection functions
615 series ANSI 705