Parameter Values (Range) Unit Step Default Description
Ng Seq A low low Lim 0.00...40.00 xIn 1 0.00 Low alarm current limit for negative sequence
current
Ng Seq A deadband 100...100000 1 2500 Deadband configuration value for negative
sequence current for integral calculation.
(percentage of difference between min and
max as 0,001 % s)
Zro A Hi high Lim
0.00...40.00 xIn 1 0.20 High alarm current limit for zero sequence
current
Zro A High limit 0.00...40.00 xIn 1 0.05 High warning current limit for zero sequence
current
Zro A low limit 0.00...40.00 xIn 1 0.00 Low warning current limit for zero sequence
current
Zro A low low Lim 0.00...40.00 xIn 1 0.00 Low alarm current limit for zero sequence
current
Zro A deadband 100...100000 1 2500 Deadband configuration value for zero
sequence current for integral calculation.
(percentage of difference between min and
max as 0,001 % s)
8.1.9.5 Monitored data
Table 830: I1,I2,I0 Monitored data
Name
Type Values (Range) Unit Description
I2-A FLOAT32 0.00...40.00 xIn Measured negative sequence
current
I1-A FLOAT32 0.00...40.00 xIn Measured positive sequence
current
I0-A FLOAT32 0.00...40.00 xIn Measured zero sequence
current
I2_INST FLOAT32 0.00...40.00 xIn Negative sequence current
amplitude, instantaneous
value
I2_ANGL
FLOAT32 -180.00...180.00 deg Negative sequence current
angle
I2_DB FLOAT32 0.00...40.00 xIn Negative sequence current
amplitude, reported value
I2_RANGE Enum 0=normal
1=high
2=low
3=high-high
4=low-low
Negative sequence current
amplitude range
I1_INST FLOAT32 0.00...40.00 xIn Positive sequence current
amplitude, instantaneous
value
I1_ANGL
FLOAT32 -180.00...180.00 deg Positive sequence current
angle
Table continues on next page
Section 8 1MAC059074-MB A
Measurement functions
922 615 series ANSI