4.5.3.7 Settings
Table 534: 59N,59G Group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Pickup value 0.010...1.000 xUn 0.001 0.030 Pickup value
Trip delay time 40...300000 ms 1 40 Trip delay time
Table 535: 59N,59G Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
VG/V0 Select 1=Measured VG
2=Calculated V0
1=Measured VG Selection for used VG/V0 signal
Table 536: 59N,59G Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time
4.5.3.8 Monitored data
Table 537: 59N,59G Monitored data
Name
Type Values (Range) Unit Description
PICKUP_DUR FLOAT32 0.00...100.00 % Ratio of pickup time / trip time
59N,59G Enum 1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
4.5.3.9 Technical data
Table 538: 59N, 59G Technical data
Characteristic
Value
Operation accuracy Depending on the frequency of the measured
voltage: f
n
±2 Hz
±1.5% of the set value or ±0.002 × V
n
Pickup time
1)2)
Minimum Typical Maximum
V
Fault
= 2 × set
Pickup
value
48 ms 51 ms 54 ms
Table continues on next page
1MAC059074-MB A Section 4
Protection functions