4.8.1.9 Technical data
Table 628: 32U Technical data
Characteristic
Value
Operation accuracy
1)
Depending on the frequency of the measured
current and voltage:
f
n
±2 Hz
Power measurement accuracy ±3% of the set value
or ±0.002 × S
n
Phase angle: ±2°
Pickup time
2)3)
Typically 45 ms
Reset time Typically 30 ms
Reset ratio Typically 1.04
Trip time accuracy ±1.0% of the set value of ±20 ms
Suppression of harmonics -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
1)
Measurement mode
= “Pos Seq” (default)
2) V = V
n
, f
n
= 50 Hz, results based on statistical distribution of 1000 measurements
3) Includes the delay of the signal output contact
4.8.2 Reverse power/directional overpower protection 32R/32O
4.8.2.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEE C37.2
device number
Reverse power/directional overpower
protection
DOPPDPR P>/Q> 32R/32O
4.8.2.2 Function block
TRIP
PICKUP
32R/32O
I_A
I_B
I_C
V_A
V_B
V_C
BLOCK
GUID-BBDFCB16-ED05-4ADF-94C6-8C56350F5FCD V1 EN
Figure 360: Function block
Section 4 1MAC059074-MB A
Protection functions
724 615 series ANSI
Technical Manual