8.1.4.3 Signals
Table 794: IA,IB,IC Input signals
Name
Type Default Description
I_A SIGNAL 0 Phase A current
I_B SIGNAL 0 Phase B current
I_C SIGNAL 0 Phase C current
BLOCK BOOLEAN 0=False Block signal for all binary outputs
Table 795: IA,IB,IC Output signals
Name Type Description
HIGH_ALARM BOOLEAN High alarm
HIGH_WARN BOOLEAN High warning
LOW_WARN BOOLEAN Low warning
LOW_ALARM BOOLEAN Low alarm
8.1.4.4 Settings
Table 796: IA,IB,IC Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
Num of phases 1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3 Number of phases required by limit supervision
A high high limit 0.00...40.00 xIn 1 1.40 High alarm current limit
A high limit 0.00...40.00 xIn 1 1.20 High warning current limit
A low limit 0.00...40.00 xIn 1 0.00 Low warning current limit
A low low limit 0.00...40.00 xIn 1 0.00 Low alarm current limit
A deadband 100...100000 1 2500 Deadband configuration value for integral
calculation. (percentage of difference between
min and max as 0,001 % s)
Table 797: IA,IB,IC Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Measurement mode 1=RMS
2=DFT
2=DFT Selects used measurement mode