Table 253: 67/50P Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time
Minimum trip time 20...60000 ms 1 20 Minimum trip time for IDMT curves
Allow Non Dir 0=False
1=True
0=False Allows prot activation as non-dir when dir info is
invalid
Measurement mode 1=RMS
2=DFT
3=Peak-to-Peak
2=DFT Selects used measurement mode
Min trip current 0.01...1.00 xIn 0.01 0.01 Minimum trip current
Min trip voltage 0.01...1.00 xUn 0.01 0.01 Minimum trip voltage
4.1.2.10 Monitored data
Table 254: 67/51P Monitored data
Name Type Values (Range) Unit Description
PICKUP_DUR FLOAT32 0.00...100.00 % Ratio of pickup time / trip time
FAULT_DIR Enum 0=unknown
1=forward
2=backward
3=both
Detected fault direction
DIRECTION Enum 0=unknown
1=forward
2=backward
3=both
Direction information
DIR_A Enum 0=unknown
1=forward
2=backward
-1=both
Direction phase A
DIR_B Enum 0=unknown
1=forward
2=backward
-1=both
Direction phase B
DIR_C Enum 0=unknown
1=forward
2=backward
-1=both
Direction phase C
ANGLE_A FLOAT32 -180.00...180.00 deg Calculated angle difference,
Phase A
ANGLE_B FLOAT32 -180.00...180.00 deg Calculated angle difference,
Phase B
Table continues on next page
1MAC059074-MB A Section 4
Protection functions
615 series ANSI 255
Technical Manual