EasyManua.ls Logo

ABB 615 Series - Technical Data

ABB 615 Series
1196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.6.1.9 Technical data
Table 594: 81 Technical data
Characteristic
Value
Operation accuracy f>/f< ±5 mHz
df/dt ±50 mHz/s (in range |df/dt| <5 Hz/s)
±2.0% of the set value (in range 5 Hz/s < |df/dt| < 15
Hz/s)
Pickup time
f>/f< <80 ms
df/dt <120 ms
Reset time <150 ms
Trip time accuracy ±1.0% of the set value or ±30 ms
4.6.1.10 Technical revision history
Table 595: 81 Technical revision history
Technical revision Change
B Step value changed from 0.001 to 0.0001 for the
Pickup value Freq>
and
Pickup value Freq<
settings.
C df/dt setting step changed from 0.005 ×Fn /s to
0.0025 ×Fn /s.
D Internal improvement.
4.7 Impedance protection
4.7.1 Out-of-step protection 78
4.7.1.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Out of step protection OOSRPSB φ> 78
1MAC059074-MB A Section 4
Protection functions
615 series ANSI 685
Technical Manual

Table of Contents

Other manuals for ABB 615 Series

Related product manuals