6.2.7 Settings
Table 742: CCM Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Enable / Disable
Pickup value 0.05...0.20 xIn 0.01 0.05 Minimum trip current differential level
Table 743: CCM Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Max alarm current 1.00...5.00 xIn 0.01 1.50 Block of the function at high phase current
6.2.8 Monitored data
Table 744: CCM Monitored data
Name Type Values (Range) Unit Description
I_DIFF FLOAT32 0.00...40.00 xIn Differential current
CCM Enum 1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
6.2.9 Technical data
Table 745: CCM Technical data
Characteristic
Value
Trip time
1)
<30 ms
1) Including the delay of the output contact
6.2.10 Technical revision history
Table 746: CCM Technical revision history
Technical revision
Change
B Internal improvement
C Internal improvement
D Internal improvement
1MAC059074-MB A Section 6
Supervision functions
615 series ANSI 853
Technical Manual