5.3.7 Settings
Table 687: 86/94 Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
Trip pulse time 20...60000 ms 1 250 Minimum duration of trip output signal
Trip output mode 1=Non-latched
2=Latched
3=Lockout
1=Non-latched Select the operation mode for trip output
5.3.8 Monitored data
Table 688: 86/94 Monitored data
Name Type Values (Range) Unit Description
86/94 Enum 1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
5.3.9 Technical revision history
Table 689: 86/94 Technical revision history
Technical revision
Change
B -
C -
D Internal improvement.
E Setting
Trip output mode
default setting is changed
to "Latched".
F Internal improvement.
5.4 High-impedance fault detection HIZ
5.4.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
High-impedance fault detection PHIZ HIF HIZ
Section 5 1MAC059074-MB A
Protection related functions
788 615 series ANSI