8.1.7.4 Settings
Table 817: VG Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
V Hi high limit res 0.00...4.00 xUn 1 0.20 High alarm voltage limit
V high limit res 0.00...4.00 xUn 1 0.05 High warning voltage limit
V deadband res 100...100000 1 10000 Deadband configuration value for integral
calculation. (percentage of difference between
min and max as 0,001 % s)
Table 818: VG Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Measurement mode 1=RMS
2=DFT
2=DFT Selects used measurement mode
8.1.7.5 Monitored data
Table 819: VG Monitored data
Name
Type Values (Range) Unit Description
VG-kV FLOAT32 0.00...4.00 xUn Measured residual voltage
BLOCK BOOLEAN 0=False
1=True
Block signal for all binary
outputs
HIGH_ALARM BOOLEAN 0=False
1=True
High alarm
HIGH_WARN BOOLEAN 0=False
1=True
High warning
VG_INST FLOAT32 0.00...4.00 xUn Ground voltage Amplitude,
magnitude of instantaneous
value
VG_ANGL
FLOAT32 -180.00...180.00 deg Residual voltage angle
VG_DB FLOAT32 0.00...4.00 xUn Ground voltage Amplitude,
magnitude of reported value
VG_DMD FLOAT32 0.00...4.00 xUn Demand value of residual
voltage
VG_RANGE Enum 0=normal
1=high
2=low
3=high-high
4=low-low
Ground voltage Amplitude
range
1MAC059074-MB A Section 8
Measurement functions
615 series ANSI 917
Technical Manual