Table 205: SCHLCCH3 output signals
Parameter Values (Range) Unit Step Default Description
CH3LIV True
False
Status of Ethernet channel X3/LAN. Value
is "True" if the port is receiving Ethernet
frames. Valid only when
Redundant mode
is set to "None" or port is not one of the
redundant ports (LAN A or LAN B).
LNK3LIV
Up
Down
Link status of Ethernet port X3/LAN.
3.20.2.4 Settings
Table 206: Port mode settings
Parameter Values (Range) Unit Step Default Description
Port 1 Mode Off
On
On Mode selection for rear port(s). If port is not
used, it can be set to “Off”. Port cannot be
set to “Off” when
Redundant mode
is
“HSR” or “PRP” and port is one of the
redundant ports (LAN A or LAN B) or when
port is used for line differential
communication.
Port 2 Mode
Off
On
On Mode selection for rear port(s). If port is not
used, it can be set to “Off”. Port cannot be
set to “Off” when
Redundant mode
is
“HSR” or “PRP” and port is one of the
redundant ports (LAN A or LAN B).
Port 3 Mode
Off
On
On Mode selection for rear port(s). If port is not
used, it can be set to “Off”. Port cannot be
set to “Off” when
Redundant mode
is
“HSR” or “PRP” and port is one of the
redundant ports (LAN A or LAN B).
3.20.2.5 Monitored data
Monitored data is available in six locations.
Monitoring/Communication/Ethernet/Activity/CH1LIV
Monitoring/Communication/Ethernet/Activity/CH2LIV
Monitoring/Communication/Ethernet/Activity/CH3LIV
Monitoring/Communication/Ethernet/Link statuses/LNK1LIV
Monitoring/Communication/Ethernet/Link statuses/LNK2LIV
Monitoring/Communication/Ethernet/Link statuses/LNK3LIV
1MAC059074-MB A Section 3