EasyManua.ls Logo

ABB 615 Series - Application

ABB 615 Series
1196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter description Parameter name
Variation Ph B start time stamp (phase B variation
start time moment)
Var Dur Ph B time
Variation duration Ph C Variation Dur Ph C
Variation Ph C start time stamp (phase C variation
start time moment)
Var Dur Ph C time
Current magnitude Ph A preceding variation Var current Ph A
Current magnitude Ph B preceding variation Var current Ph B
Current magnitude Ph C preceding variation Var current Ph C
Table 927: Enumeration values for the recorded data parameters
Setting name Enum name Value
Variation type Swell 1
Variation type Dip 2
Variation type Swell + dip 3
Variation type Interruption 4
Variation type Swell + Int 5
Variation type Dip + Int 6
Variation type Swell+dip+Int 7
10.3.6 Application
Voltage variations are the most typical power quality variations on the public electric
network. Typically, short-duration voltage variations are defined to last more than half of
the nominal frequency period and less than one minute (European Standard EN 50160 and
IEEE Std 1159-1995).
These short-duration voltage variations are almost always caused by a fault condition.
Depending on where the fault is located, it can cause either a temporary voltage rise
(swell) or voltage drop (dip). A special case of voltage drop is the complete loss of voltage
(interruption).
PQSS is used for measuring short-duration voltage variations in distribution networks.
The power quality is evaluated in the voltage waveform by measuring the voltage swells,
dips and interruptions.
Section 10 1MAC059074-MB A
Power quality measurement functions
1054 615 series ANSI
Technical Manual

Table of Contents

Other manuals for ABB 615 Series

Related product manuals