10.4.8 Monitored data
Table 941: PQVUB Monitored data
Name
Type Values (Range) Unit Description
3S_MN_UNB FLOAT32 0.00...150.00 % Non sliding 3 second mean
value of voltage unbalance
10MIN_MN_UNB FLOAT32 0.00...150.00 % Sliding 10 minutes mean value
of voltage unbalance
PCT_UNB_VAL FLOAT32 0.00...150.00 % Limit below which percentile
unbalance of the values lie
MAX_UNB_VAL FLOAT32 0.00...150.00 % Maximum voltage unbalance
measured in the observation
period
MAX_UNB_TIME
Timestamp Time stamp at which
maximum voltage unbalance
measured in the observation
period
PR_STR_TIME
Timestamp Time stamp of starting of the
previous observation period
PR_END_TIME Timestamp Time stamp of end of previous
observation period
Alarm high mean Dur FLOAT32 0.000...3600.000 s Time duration for alarm high
mean unbalance
Max unbalance Volt FLOAT32 0.00...150.00 % Maximum 3 seconds
unbalance voltage
Time Max Unb Volt Timestamp Time stamp of maximum
voltage unbalance
Alarm high mean Dur FLOAT32 0.000...3600.000 s Time duration for alarm high
mean unbalance
Max unbalance Volt FLOAT32 0.00...150.00 % Maximum 3 seconds
unbalance voltage
Time Max Unb Volt Timestamp Time stamp of maximum
voltage unbalance
Alarm high mean Dur FLOAT32 0.000...3600.000 s Time duration for alarm high
mean unbalance
Max unbalance Volt FLOAT32 0.00...150.00 % Maximum 3 seconds
unbalance voltage
Time Max Unb Volt Timestamp Time stamp of maximum
voltage unbalance
PQVUB Enum 1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
1MAC059074-MB A Section 10
Power quality measurement functions
615 series ANSI 1071
Technical Manual