8.1.4.5 Monitored data
Table 798: IA,IB,IC Monitored data
Name
Type Values (Range) Unit Description
IA-A FLOAT32 0.00...40.00 xIn Measured current amplitude
phase A
IB-A FLOAT32 0.00...40.00 xIn Measured current amplitude
phase B
IC-A FLOAT32 0.00...40.00 xIn Measured current amplitude
phase C
Max demand IA FLOAT32 0.00...40.00 xIn Maximum demand for Phase
A
Max demand IB FLOAT32 0.00...40.00 xIn Maximum demand for Phase
B
Max demand IC FLOAT32 0.00...40.00 xIn Maximum demand for Phase
C
Min demand IA FLOAT32 0.00...40.00 xIn Minimum demand for Phase A
Min demand IB FLOAT32 0.00...40.00 xIn Minimum demand for Phase B
Min demand IC FLOAT32 0.00...40.00 xIn Minimum demand for Phase C
Time max demand IA Timestamp Time of maximum demand
phase A
Time max demand IB Timestamp Time of maximum demand
phase B
Time max demand IC Timestamp Time of maximum demand
phase C
Time min demand IA Timestamp Time of minimum demand
phase A
Time min demand IB Timestamp Time of minimum demand
phase B
Time min demand IC Timestamp Time of minimum demand
phase C
BLOCK BOOLEAN 0=False
1=True
Block signal for all binary
outputs
HIGH_ALARM BOOLEAN 0=False
1=True
High alarm
HIGH_WARN BOOLEAN 0=False
1=True
High warning
LOW_WARN BOOLEAN 0=False
1=True
Low warning
LOW_ALARM BOOLEAN 0=False
1=True
Low alarm
I_INST_A FLOAT32 0.00...40.00 xIn IA Amplitude, magnitude of
instantaneous value
I_ANGL_A FLOAT32 -180.00...180.00 deg IA current angle
Table continues on next page