Table 779: OPTM Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Initial value 0...299999 h 1 0 Initial value for operation time supervision
Operating time hour 0...23 h 1 0 Time of day when alarm and warning will occur
Operating time mode 1=Immediate
2=Timed Warn
3=Timed Warn Alm
1=Immediate Operating time mode for warning and alarm
6.6.8 Monitored data
Table 780: OPTM Monitored data
Name Type Values (Range) Unit Description
OPTM Enum 1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
OPR_TIME INT32 0...299999 h Total operation time in hours
6.6.9 Technical data
Table 781: OPTM Technical data
Description
Value
Motor runtime measurement accuracy
1)
±0.5%
1) Of the reading, for a stand-alone relay, without time synchronization
6.6.10 Technical revision history
Table 782: OPTM Technical revision history
Technical revision
Change
B Internal improvement.
C Internal improvement.
D Internal improvement.
1MAC059074-MB A Section 6
Supervision functions
615 series ANSI 877
Technical Manual