Table 503: 46M Output signals
Name Type Description
TRIP BOOLEAN Trip
PICKUP BOOLEAN Pickup
BLK_RESTART BOOLEAN Overheated machine reconnection blocking
4.4.4.8 Settings
Table 504: 46M Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Pickup value 0.01...0.50 xIn 0.01 0.20 Pickup value
Operating curve type 5=ANSI DT
15=IEC DT
17=Inv. Curve A
18=Inv. Curve B
15=IEC DT Selection of time delay curve type
Machine time Mult 5.0...100.0 0.1 5.0 Machine related time constant
Trip delay time 100...120000 ms 10 1000 Trip delay time
Table 505: 46M Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
Maximum trip time 500000...7200000 ms 1000 1000000 Max trip time regardless of the inverse
characteristic
Minimum trip time 100...120000 ms 1 100 Minimum trip time for IDMT curves
Cooling time 5...7200 s 1 50 Time required to cool the machine
Table 506: 46M Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Rated current 0.30...2.00 xIn 0.01 1.00 Rated current (Ir) of the machine (used only in
the IDMT)
Reset delay time 0...60000 ms 1 20 Reset delay time
Section 4 1MAC059074-MB A
Protection functions
608 615 series ANSI
Technical Manual